Close to silicon
The idea
A cold plate is a solid structure that transfers heat into flowing liquid.2 In direct-to-silicon cooling, a separate silicon cold plate bonds to the back of the device, enclosing liquid passages against its surface.2,4 The active circuitry stays on the opposite face, outside the coolant.2,5
A conventional lidded package conducts heat through the die, interface materials, lid and cold-plate base before reaching liquid.2 A thermal interface material, or TIM, fills gaps between assembled surfaces but adds thermal resistance.2 Direct bonding removes the cold-plate TIM, and the silicon cooler can replace the lid and its interfaces.2,4
Drag to turn
Heat and flow
How it works
Heat crosses the device silicon and enters liquid along the channel roof.2,7 Heat also spreads through bonded lands into the cap and channel walls, adding wetted area.1,2,7 The remaining silicon beneath the channel floor provides support; it is outside the direct roof-to-liquid heat path.2,6
Small channels shorten the distance over which heat diffuses into the moving liquid.1 For comparable laminar flows, reducing the hydraulic diameter increases the heat-transfer coefficient, which relates heat flux to the wall-to-liquid temperature difference.1 Hydraulic diameter expresses channel size as four times its cross-sectional area divided by its wetted perimeter.1
An inlet manifold distributes liquid among the channels, and an outlet manifold collects the warm return flow.5 Straight channels can be fed through headers at their ends.5,7 Distributed manifolds instead feed shorter channel segments, reducing the distance liquid travels through each narrow passage.5,8
Narrow passages also resist flow, so channel geometry and manifold layout determine both cooling and pressure drop.7,8 Hydraulic pumping power is pressure drop multiplied by volumetric flow: P = Δp × Q.7,8 Electrical pump power is higher because the pump and the rest of the loop introduce additional losses.7,8
Thermal resistance describes temperature rise per unit heat load: R = (T − Tin)/P, in K/W.1,9 Here T is the device temperature, Tin is inlet coolant temperature, and P is heat load.1,9 Heat flux is power divided by heated area, so area-normalized resistance uses heat flux instead of power and has units K·cm²/W.1,9
1981 onward
A short history
Silicon microchannel cooling began with channels formed directly in a heated silicon substrate.1 Microfluidics confines and controls liquid in small channels.5,8 Later work explored separate coolers, liquid-cooled interposers and cooling integrated into semiconductor packages.3,9,10 An interposer is an intermediate substrate that carries connections between devices and the package.10
- Foundations
- 1981
Water cooling in silicon
Tuckerman and Pease removed 790 W/cm² with a maximum 71 K rise above inlet water, using vertical channels in (110) silicon.1
- 2007
The attachment interface matters
IBM reported a multipass silicon cooler with epoxy or indium attachment, showing how the interface influences overall thermal resistance.9
- Embedded cooling
- 2012
Cooling within and between chips
DARPA launched the ICECool solicitation for cooling within and between chips, establishing an embedded-cooling research program.11
- 2015
- 2020
- Package integration
- 2024
Kilowatt package cooling
TSMC reported a silicon-integrated micro-cooler handling a uniform 2,000 W load with 40 °C inlet water.3
- 2025
- 2026
Measured performance
Recent results
Adeia’s 2025 study directly bonded a separate silicon cold plate to the device.2 At 150–200 W/cm² and more than 1,000 W die power, it reported about 70% lower junction-to-inlet resistance than its comparison configuration.2 That result includes the benefit of changing the attachment interface.2
| Study | Construction | Heat load | Conditions and result |
|---|---|---|---|
| EPFL, 20208 | Gallium nitride electronics integrated with silicon microfluidics8 | More than 1,700 W/cm²8 | Hydraulic pumping power: 0.57 W/cm² at this heat-flux result8 |
| TSMC, 20243 | Silicon-integrated, compartmentalized micropillars3 | 2,000 W total; 320 W/cm² uniform3 | 40 °C inlet water; pumping power described as much less than 10 W in the published abstract3 |
| Adeia, 20252 | Separate silicon cold plate directly bonded to the device2 | More than 1,000 W; 150–200 W/cm²2 | About 70% lower junction-to-inlet resistance than the study’s comparison configuration2 |
| KAIST / Georgia Tech, 202614 | Manifold microchannels embedded in a thermal test chip14 | More than 2,000 W/cm²14 | Room-temperature water; junction below 100 °C; 7.8 kPa total pressure drop, reported in the abstract14 |
| KAIST / Georgia Tech, 202614 | Same cooler, separate efficiency operating point14 | 1,180 W/cm²14 | Cooling coefficient of performance 106,000, with a 60 K maximum-rise constraint, reported in the abstract14 |
Water-cooled demonstrations use different channel structures, heated areas and operating conditions.2,3,8,14
The 2026 Adeia manuscript uses computational fluid dynamics, a numerical model of fluid flow and heat transfer, checked against experiments.7 Its optimized flow layout reaches 78.4 °C and 8 psi pressure drop, versus 90.8 °C and 25 psi for the baseline.7 Those layout comparisons are model results at fixed total flow.7
Microsoft reported laboratory microfluidic cooling with up to threefold better heat removal and a 65% reduction in maximum temperature rise in 2025.16 These company-reported improvements depend on the tested configuration; the percentage describes temperature rise above a reference, not absolute temperature.16
A meaningful thermal comparison holds inlet temperature, heat load and flow conditions together with the measured pressure drop.2,7 Peak heat removal and peak cooling efficiency can occur at different operating points.8,14 Thermal performance and long-term package reliability require separate measurements.4,16
Two wafers
The fabrication route
Glance Foundry wet-etches straight channels in a (100) silicon cap wafer using potassium hydroxide (KOH) or tetramethylammonium hydroxide (TMAH).4,6 The (100) designation identifies the wafer’s crystal plane.6 The cap aligns to the device wafer in a mask aligner, with the second wafer held in place of the mask.17 Radio-frequency (RF) oxygen-plasma activation prepares the surfaces for direct bonding, followed by a low-temperature anneal, or heat treatment.6,18
The two wafers remain separate through channel etching, port formation and surface preparation.4,6 This keeps the cap’s hot masking processes and alkaline etchants away from the device circuitry.5,6,19 The cap’s flat sealing lands then contact the polished device backside to enclose the channels.2,6
Crystal geometry
Channels by wet etching
Anisotropic wet etching removes silicon at different rates along different crystal planes.6 On a (100) wafer, the slowly etched {111} planes form walls at 54.74° to the wafer surface.6 Properly oriented straight openings therefore develop sloped walls and a flat bottom until the opposing walls meet.6
For ideal facets, bottom width equals top width minus √2 times depth.6 The V-groove limit is top width divided by √2, so a 100 µm opening reaches approximately 70.7 µm depth.6 The representative 300 µm opening at 100 µm depth leaves a 158.6 µm floor and 100 µm bonding lands at 400 µm pitch.6
KOH and TMAH both form these crystal-defined walls, but bath composition and temperature change their etch rates.6,21 TMAH avoids introducing potassium; compatibility still depends on the exposed materials.6,19,21 Mask thickness accounts for the entire channel and port etch, including erosion and defects.6,20
| Etchant | Concentration and temperature | Example silicon rate | Time for 100 µm |
|---|---|---|---|
| KOH21,22 | 25–30 wt% at 80 °C21,22,23 | Approximately 60–80 µm/h21,22 | Calculated 75–100 minutes, excluding initiation and rate drift21,22 |
| TMAH21 | 25 wt% at 80 °C21 | Approximately 20 µm/h21 | Calculated 300 minutes, excluding initiation and rate drift21 |
Published bath examples; actual depth control uses a measured rate from the working bath.21,22,23
- 01
Wet-etch the channels
A temperature-controlled KOH or TMAH bath removes the exposed silicon to the target depth.6,21 Depth, floor width, surface finish and sealing lands are inspected after etching.6 Thorough rinsing and a compatible metal-ion clean control alkaline contamination.6,24
Representative channel: 300 µm top width, 100 µm depth, 400 µm pitch6
- 02
Open the fluid ports
Backside mask windows align to the end headers, then wet etching opens inlet and outlet ports through the remaining silicon.4,6 Protection of the channel face and control of breakthrough limit further attack inside the channels.6
Calculated opening: about 766 µm for a 200 µm exit through 400 µm silicon6
- 03
Strip and clean
Sacrificial nitride and contaminated mask material are removed while the bonding lands retain their polish.6,20 Hot phosphoric acid strips nitride; a compatible fluoride-based process removes oxide where required.20,25 A final clean prepares native-oxide silicon or a controlled oxide surface for bonding.6
Published nitride-strip temperature: approximately 160–165 °C20,25
Corners at headers and channel intersections can undercut faster than long, straight edges.6 Sacrificial corner extensions compensate for this retreat, with dimensions established by bath-specific test patterns.6 The {111} walls also etch slowly, so a V-groove is only approximately self-limiting.6
Bonding lands must remain free of scratches, particles, dried residues and adhesive contact.4,6 After KOH, an acid-based metal-ion clean addresses potassium contamination before final bonding preparation.6,24,25 Clean handling and covered storage preserve those surfaces between operations.4,6
Surface to surface
Alignment and bonding
Direct bonding joins prepared surfaces without an adhesive layer.6 In this route, the surfaces are hydrophilic, meaning they attract water, and oxygen-plasma treatment creates or modifies their thin surface oxide.6,18 The resulting silicon-to-silicon assembly can therefore contain oxide at the bonded interface.6
- 01
Prepare the device wafer
The polished device backside becomes the channel roof; frontside circuits remain protected during cleaning.2,6,19 A thermal test wafer uses patterned resistive heaters and temperature sensors to measure cooling under known loads.5 Both mating surfaces are checked for roughness, particles and wafer bow.6,26
Published test stack: 10 nm chromium / 350 nm platinum on 200–500 nm oxide5
Local roughness and wafer shape both affect whether the surfaces make intimate contact.6,26 Published hydrophilic bonding guidance gives root-mean-square roughness below 0.5 nm, measured with an atomic force microscope.26 Particles can create unbonded regions much larger than themselves, making the final particle, organic and metal-ion clean essential.6
Dziuban’s Bonding in Microsystem Technology (2006), pages 151–153, describes oxygen-plasma-assisted silicon-to-silicon bonding well below 300 °C.6 Radio-frequency oxygen plasma activates both mating faces before rinsing, drying and contact.18 Plasma exposure and the later anneal are matched to the device’s surface chemistry, electrical sensitivity and thermal budget.6,18,27
- 01
Activate both bond faces
Both cleaned faces receive RF O2 plasma in a parallel-plate chamber operated in reactive-ion-etching mode.18,28 Deionized-water rinsing and clean drying leave hydrated surfaces without visible droplets.6,18 Plasma exposure is qualified against surface damage, roughness and bond quality.6,18,28
Development starting point: 200 W, 200 mTorr, 60–120 seconds; reactor-specific18
Gatzen, Saile & Leuthold describe wafer-to-wafer alignment in Micro and Nano Fabrication: Tools and Processes (2015), page 447.17 A contact/proximity mask aligner uses a bonding fixture to hold the second wafer in the position normally occupied by the mask.17 Backside or infrared optics register the wafer marks, while clamps and spacers preserve alignment before contact.17
Infrared alignment views buried marks through silicon, so mark placement must account for metal coverage and wafer transmission.6,17 The alignment budget includes translation, rotation and movement during clamping or transfer.17 Registration marks measured after bonding reveal the final offset.17
- 01
- 02
- 03
Anneal at low temperature
A controlled ramp, dwell and cooldown strengthen the interface within the device’s allowed temperature range.6,27 Witness samples establish the needed time and temperature, while infrared inspection tracks unbonded regions after annealing.6,18,28
Development window: 200–250 °C for 1–2 hours, subject to coupon qualification6,18
Infrared images locate voids, while mechanical tests measure adhesion.6,18,28 Crack-opening tests on witness wafers estimate interfacial energy in J/m²; tensile tests measure strength in MPa.6,18 These are distinct measurements, and patterned channels change the bonded area and mechanical response.6,18
Assembly and testing
After bonding
- 01
An external manifold connects the cap’s backside ports to the liquid loop.4 Its supports carry tubing loads, and coolant-compatible seals contain the flow at each connection.4 The manifold’s pressure loss and flow distribution contribute to the assembled cooler’s performance.4,7
Leak and pressure tests evaluate the complete fluid circuit before powered thermal testing.4,18 Proof pressure and dwell reflect the intended operating conditions and package strength, while destructive burst tests use sacrificial units.4,18 Bond imaging alone cannot establish liquid tightness.6,18
Calibrated heaters and temperature sensors measure the thermal response across inlet temperatures, flow rates and heat loads.2,5,7 Each operating point records heat input, heated area, inlet and outlet temperatures, peak device temperature, flow and pressure drop.2,7 Coolant heat pickup provides an energy-balance check against heater power and losses to the surroundings.2,7
- Thermal record: peak and average temperatures, thermal resistance, heated area and measurement uncertainty at each operating point.2,7
- Hydraulic record: flow, pressure drop and pumping demand for the assembled cooler and its manifold.4,7
- Reliability record: leak, thermal and bond-inspection results after pressure cycling, thermal cycling and coolant exposure.4,16
Filtration, coolant cleanliness and control of trapped gas protect the narrow flow passages.4,7,10 Continued testing checks for deposits, corrosion, blockage and changes in external seals.4,16 The operating envelope belongs to the tested combination of channel geometry, bond, coolant and package.4,16