01 / 07
Cooling limits computing density
Three measures matter
02 / 07
Why liquid cooling is expanding
Higher accelerator power and dense, interconnected racks make cooling a package, rack, and facility problem.6,8
Published rack figures
| Example | Figure | What it describes |
|---|---|---|
| 2024 reference design | 120 kW | Cooling capacity.44 |
| Published rack datasheet | 132–140 kW | Specified operating power.45 |
| AI blueprint available by November 2026 | 227 kW | Cooling design capacity.46 |
| From 2027; roadmap announced May 2025 | 1 MW | Power-distribution target.47 |
Cooling capacities, equipment power specifications, and roadmap targets describe different limits.44,45,46,47
In Uptime’s 2025 survey, 22% of the 512 respondents to the cooling-type question reported using direct liquid cooling.16
Annual data-center electricity use
Worldwide
International Energy Agency · April 2026 update48
- 2025 Estimate
- 485 TWh/year
- 2030 Projection
- about 950 TWh/year
Energy efficiency and water
Power usage effectiveness (PUE) divides total facility energy by IT equipment energy.14 It does not measure useful computing output or water consumption.3,14
For 2023, Berkeley Lab estimated U.S. data-center water consumption at 66 billion liters on site, plus nearly 800 billion liters associated with electricity generation.3
03 / 07
Inside a cold-plate cooling loop
In a cold-plate system, heat crosses the processor package and cooling interfaces into a sealed heat exchanger with internal coolant channels.8,15 The single-phase example below keeps the coolant liquid as it warms.17
Equal heat capacity
For the same temperature rise
Getting heat into the coolant
The heat-transfer coefficient h describes heat transfer from the surface into the moving coolant.9 It depends on flow, channel geometry, and coolant properties.11
Single-phase cooling relationships
Heat carried by single-phase coolant
Heat transferred from the surface
- Heat-transfer rate (W)
- Coolant mass flow rate (kg/s)
- Coolant specific heat capacity (J/(kg·K))
- Coolant temperature rise (K)
- Surface-to-fluid heat-transfer coefficient (W/(m²·K))
- Heat-transfer area (m²)
- Appropriate surface-to-fluid temperature difference (K)
The first equation describes single-phase coolant warming. Its inlet-to-outlet temperature rise differs from the surface-to-fluid temperature difference in the second equation.7
Two separate circuits
A coolant distribution unit (CDU) commonly circulates the electronics coolant and transfers its heat to a separate facility water loop.19 The electronics loop can then use its own pressure and coolant chemistry.19
Example: a single-phase cold-plate loop
04 / 07
Liquid cooling approaches
Cooling approaches differ in where liquid collects heat and whether it changes phase.17
Cold plates
Coolant flows through sealed plates on processor packages.15,17
Single-phase designs often retain some air cooling.15
Immersion
Rear-door heat exchangers
A water-cooled coil captures server exhaust heat.5
Server fans and heat sinks remain.5
Phase options for cold plates and immersion
05 / 07
Six decades of liquid cooling
Selected milestones, 1964–2026.
- Mainframes and early research
- 1964–1965
Water-cooled mainframes
IBM announced water-cooled heat exchangers between board stacks in 1964; a separate computer-water circuit followed in 1965.54
- 1980
- 1981
Silicon microchannels
Tuckerman and Pease demonstrated water cooling through silicon microchannels.7
- 1985
Immersion in supercomputing
Cray-2 cooled its submerged electronics with an electrically insulating liquid.57
- 1994–1995
- Rack cooling and heat reuse
- 2005
Cooling server exhaust
Rear-door heat exchangers captured server exhaust heat in water while the electronics remained air-cooled.54
- 2010–2012
- AI deployment and new research
- 2018
Liquid-cooled AI accelerators
Google deployed liquid cooling for its TPU v3 AI accelerators.24
- 2025Prototype
Cooling through the back of a chip
Microsoft announced a microfluidic prototype with coolant channels etched into the back of a chip.23
- 2026Validation target
A 1 MW cooling target
COOLERCHIPS 1.5 set a goal to validate cooling systems against heat loads of 1 MW per rack.61
06 / 07
Investment in cooling
Three kinds of capital
Selected funding and acquisition events
Nominal U.S. dollars · logarithmic chart scale
| Type | Event | Amount | What the amount represents |
|---|---|---|---|
| Public support | U.S. Department of Energy / COOLERCHIPS (May 2023) | US$40 million | Funding announced for 15 selected research projects.4 |
| Public support | CHIPS / Akash Systems (November 2024) | Up to US$18.2 million proposed | Proposed direct funding under nonbinding preliminary terms for diamond-based semiconductor manufacturing.69 |
| Private financing | JetCool (October 2023) | US$17 million | Series A financing led by Bosch Ventures for development and expansion.65 |
| Private financing | LiquidStack (September 2024) | US$20 million | Series B extension from Tiger Global for manufacturing and cooling research; part of a US$35 million cumulative Series B.66 |
| Private financing | Submer (October 2024) | US$55.5 million | Growth financing secured to date; led by M&G Catalyst.67 |
| Private financing | Corintis (September 2025) | US$24 million | Series A led by BlueYard Capital for chip-cooling development and commercialization.62 |
| Private financing | Corintis (December 2025) | US$25 million | Separate financing round led by Applied Digital for chip-cooling development.70 |
| Private financing | Accelsius (January 2026) | US$65 million | Series B closing announced; Johnson Controls led, with Legrand investing.22 |
| Private financing | Iceotope (May 2026) | US$26 million | Series B led by Two Seas Capital and Barclays Climate Ventures for development and deployment.71 |
| Private financing | ZutaCore (June 2026) | US$100 million | Series C financing for two-phase cooling commercialization; the release body states US$100 million.72 |
| Acquisitions | Schneider Electric / Motivair (October 2024 agreement) | US$850 million | Announced price for a 75% stake; the deal closed in February 2025.68,79 |
| Acquisitions | Flex / JetCool (November 2024) | US$52 million estimated | Completed acquisition; estimated total consideration includes cash, loan settlement, and contingent consideration.64 |
| Acquisitions | Eaton / Boyd Thermal (March 2026) | US$9.55 billion | Completed acquisition of a broad thermal-management business; price is net of acquired cash.63 |
07 / 07
Thin films and thermal interfaces
Solid layers and contacts between the chip and coolant add thermal resistance.7,8 Reducing resistance on the fluid side increases their share of the total if they remain unchanged.7
Thermal interface materials help heat cross adjoining surfaces; solder can form a bonded metal interface.8,86
Thin-film roles
| Role | What it does |
|---|---|
| Joint surfaces | Metal finishes influence how solder joints form and age.86 |
| Diffusion barriers | Nickel can limit copper–tin interdiffusion; its effect depends on the layer stack and thermal history.86 |
| Test heaters | Deposited thin-film resistors provide controlled heat input in cooling experiments.7 |